The Satronic TMG 720-4 oil burner control box is capable of controlling and monitoring medium to high capacity forced-draught burners (tested and approved as per EN 230). It can be employed, as preferred, for multi-stage or modulating operation, with burners of any nominal rating or with stationary warm air generators (as per DIN 4794).
Specificacions:
– Refª completa: TMG 720-4 (08001U Honeywell)
– For 1- or 2-stage oil burners up to 30 kg/h throughput and intermittent operation
– Flame detection: photo resistor FZ 771 S, infrared-flicker detector IRD 1010
– Power supply: 220 – 240V
– Pre-purge time with air damper open: 30 sec
– Air damper open / close time: <60 sec
– Pre-ignition time: 30 sec or 2 sec (terminal 10)
– Safety interval (fixed): 5sec
– Postt-ignition time (fixed): 7.5 sec
– Delay second stage: 11.5 sec